ASCE 113-23 - Foundation Seismic Ties for Substation Equipment
Posted By
Samuel Moss
01-04-2024 06:57 PM
Found In
Egroup:
Peer-to-Peer Standards Exchange
\
view thread
The latest edition of the ASCE's Substation Structure Design Guide (ASCE 113-23), references ACI 318-19. Per section 18.13.4.1 of ACI 318-19 foundation seismic ties are required for piers and caissons in Seismic Design Category C, D, E and F. This provision makes sense for building design, as the columns ...